Dimmer-Control
FGD-212
Light Dimmer Switch
HW: 2 FW: 3.05:03.05
ZM5202
6.51.07
0x010F (271)
0x0102 (258)
0x1000 (4096)
ZC10-22037071
2022-03-02 16:39:14.733454
N/A
Enhanced 232 Slave
Always On Slave
Module is designed to work with various types of light sources. It may be connected to two-wire or three wire configuration so it can operate with or without neutral lead
Remotely controlled light dimming module is designed to work with various types of light sources. It may be connected to two-wire or three wire configuration so it can operate with or without neutral lead. Dimmer-Control can switch or dim connected light source either through radio waves or through the wall switch connected directly to it. New Dimmer-Control is equipped with an algorithm of smart light source detection which makes configuration easier and ensures high compatibility of the device. It may be used as a switch with non-dimmable light sources (in 3-wire connection).

Product Image
View configuration parameters (51)
1 - Minimum brightness level
This parameter is set automatically during the calibration process. The parameter can be changed manually after the calibration. The maximum brightness level (parameter 2) must be greater than the minimum brightness level (parameter 1).Size: 1 byte
Default: 1
Minimum: 1
Maximum: 98
Possible values
| From | To | Desription |
|---|---|---|
| 1 | 98 | percentage level of brightness |
2 - Maximum brightness level
This parameter is set automatically during the calibration process. The parameter can be changed manually after the calibration. The maximum brightness level (parameter 2) must be greater than the minimum brightness level (parameter 1).Size: 1 byte
Default: 99
Minimum: 2
Maximum: 99
Possible values
| From | To | Desription |
|---|---|---|
| 2 | 99 | percentage level of brightness |
3 - . Incandescence level of dimmable compact fluorescent lamps
Virtual value set as a percentage level between parameters MIN (1%) and MAX. (99%). The Dimmer-Control will set to this value after first switch on. It is required for warming up and switching dimmable compact fluorescent lamps and certain types of light sources.Size: 1 byte
Default: 1
Minimum: 1
Maximum: 99
Possible values
| From | To | Desription |
|---|---|---|
| 1 | 99 | percentage level of brightness |
4 - Incandescence time of dimmable compact fluorescent lamps
This parameter determines the time required for switching compact fluorescent lamps and certain types of light sources. Setting this parameter to 0 will disable the incandescence functionalitySize: 2 bytes
Default: 0
Minimum: 1
Maximum: 25
Possible values
| From | To | Desription |
|---|---|---|
| 1 | 25 | time of dimmable compact fluorescent lamps |
5 - Automatic control - dimming step size
This parameter defines the percentage value of dimming step during the automatic control. Automatic control is performed through: - single push-button click - double push-button click - Z-Wave control framesSize: 1 byte
Default: 0
Minimum: 1
Maximum: 99
Possible values
| From | To | Desription |
|---|---|---|
| 1 | 99 | dimming step percentage value |
6 - Automatic control - time of a dimming step
This parameter defines the time of single dimming step set in parameter 5 during the automatic control.Size: 2 bytes
Default: 1
Minimum: 0
Maximum: 255
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 255 | time of a dimming step |
7 - Manual control - dimming step size
This parameter defines the percentage value of dimming step during the manual control. Manual control is performed through holding the push-buttonSize: 1 byte
Default: 1
Minimum: 1
Maximum: 99
Possible values
| From | To | Desription |
|---|---|---|
| 1 | 99 | dimming step percentage value |
8 - Manual control - time of a dimming step
This parameter defines the time of single dimming step set in parameter 7 during the manual control.Size: 2 bytes
Default: 5
Minimum: 0
Maximum: 255
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 255 | time of a dimming step |
9 - State of the device after a power failure
The Dimmer-Control will return to the last state before power failure.Size: 1 byte
Default: 1
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | state before power failure. |
10 - Timer functionality (auto - off)
This parameter allows to automatically switch off the device after specified time from switching on the light source. It may be useful when Dimmer-Control is installed in the stairwaySize: 2 bytes
Default: 0
Minimum: 0
Maximum: 32767
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 32767 | Timer functionality (auto - off) |
11 - ALL ON/ALL OFF function
Parameter allows for activation/deactivation of Z-Wave commands enabling/disabling all devices located in direct range of the main controllerSize: 2 bytes
Default: 255
Minimum: 0
Maximum: 255
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 255 | ALL ON/ALL OFF function |
| 0 | 255 | ALL ON/ALL OFF function |
12 - Force auto-calibration
Changing value of this parameter will force the calibration process. During the calibration parameter is set to 1 or 2 and switched to 0 upon completion.Size: 2 bytes
Default: 0
Minimum: 0
Maximum: 2
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 2 | Force auto-calibration |
| 0 | 2 | Force auto-calibration |
13 - Auto-calibration status (read-only parameter)
This parameter determines operating mode of Dimmer-Control (automatic/manual settings).Size: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | Auto-calibration status (read-only parameter) |
14 - Burnt out bulb detection
Function based on the sudden power variation of a specific value, interpreted as a LOAD ERROR. Parameter 15 is relevant only when parameter 58 is set to 0 and the control mode is consistent with the mode set during the calibration process (parameter 30).Size: 1 byte
Default: 30
Minimum: 0
Maximum: 99
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 99 | Burnt out bulb detection |
15 - Time delay of a burnt out bulb (parameter 15) or overload (parameter 39) detection
Time of delay (in seconds) for power variation detection, interpreted as a LOAD ERROR or OVERLOAD detection (too much power connected to Dimmer-Control).Size: 2 bytes
Default: 5
Minimum: 0
Maximum: 255
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 255 | Time delay of a burnt out bul |
16 - Forced switch on brightness level
If the parameter is active, switching on Dimmer-Control (S1 single click) will always set this brightness level.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 99
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 99 | Forced switch on brightness level |
17 - Switch type
Choose between momentary, toggle and roller blind switch.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 2
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 2 | Choose between momentary |
18 - The value sent to associated devices on single click
This parameter defines the value sent to devices associated with Dimmer-Control after its enablingSize: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | The value sent to associated devices on single click |
19 - Assign toggle switch status to the device status
By default each change of toggle switch position results in action of Dimmer-Control (switch on/off) regardless the physical connection of conntacts.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | Assign toggle switch status to the device status |
20 - Double click option - set the brightness level to MAX
0 - double click disabled 1 - double click enabledSize: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | Double click option - set the brightness level to MAX |
21 - Command frames sent in 2nd and 3rd association groups (S1 associations)
Parameter determines, which actions will not result in sending frames to association groups. Parameter 24 values may be combined, e.g. 1+2=3 means that associations on switching ON or OFF Dimmer-Control (single click) will not be sent.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 16
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 16 | Command frames sent in 2nd and 3rd association groups (S1 associations) |
22 - Command frames sent in 4th and 5th association groups (S2 associations)
Parameter determines, which actions will not result in sending frames to association groups. Parameter 25 values may be combined, e.g. 1+2=3 means that associations on switching ON or OFF Dimmer-Control (single click) will not be sent.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 16
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 16 | Command frames sent in 4th and 5th association groups |
23 - The function of 3-way switch
Switch no. 2 controls Dimmer-Control additionally (in 3-way switch mode). Function disabled for parameter 20 set to 2 (roller blind switch).Size: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | The function of 3-way switch |
24 - Associations in Z-Wave network security mode
Parameter 27 values may be combined, e.g. 1+2=3 means that 2nd & 3rd group are sent as secureSize: 1 byte
Default: 15
Minimum: 0
Maximum: 15
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 15 | Associations in Z-Wave network security mode |
25 - Scene activation functionality
SCENE ID depends on the switch type configurations (see Table A5). Enabling scene activation functionality may cause slight delay in response to external switches and sending associations.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | Scene activation functionality |
26 - Switch functionality of S1 and S2
This parameter allows for switching the role of keys connected to S1 and S2 without changes in connection.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | Switch functionality of S1 and S2 |
27 - Load control mode
This parameter allows to set the desired load control mode. The device automatically adjusts correct control mode, but the installer may force its change using this parameter. Forced auto-calibration will set this parameter’s value to 2.Size: 1 byte
Default: 2
Minimum: 0
Maximum: 2
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 2 | Load control mode |
28 - Load control mode recognized during auto-calibration (read only
This parameter allows to set the desired load control mode. The device automatically adjusts correct control mode, but the installer may force its change using this parameter. Forced auto-calibration will set this parameter’s value to 2.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | Load control mode recognized during auto-calibration |
29 - On/Off mode
This mode is necessary while connecting non-dimmable light sources. Setting this parameter to 1 automatically ignores brightening/dimming time settings. Forced auto-calibration will set this parameter’s value to 2.Size: 1 byte
Default: 2
Minimum: 0
Maximum: 2
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 2 | On/Off mode |
30 - Dimmability of the load
his parameter contains an information about possibility of dimming the load detected during calibration procedureSize: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | Dimmability of the load |
31 - Soft-Start functionality
Time required to warm up the filament of halogen bulb.Size: 1 byte
Default: 1
Minimum: 0
Maximum: 2
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 2 | Soft-Start functionality |
32 - Auto-calibration after power on
This parameter determines the trigger of auto-calibration procedure, e.g. power on, load error, etc.Size: 1 byte
Default: 1
Minimum: 0
Maximum: 4
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 4 | Auto-calibration after power on |
33 - Behaviour of Dimmer-Control after OVERCURRENT or SURGE
Occuring of errors related to surge or overcurrent results in turning off the output to prevent possible malfunction. By default the device performs three attempts to turn on the load (useful in case of momentary, short failures of the power supply.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | Behaviour of Dimmer-Control after OVERCURRENT or SURGE |
34 - Brightness level correction for flickering loads
Correction reduces spontaneous flickering of some capacitive load (e.g. dimmable LEDs) at certain brightness levels in 2-wire installation. In countries using ripple-control, correction may cause changes in brightness. In this case it is necessary to disable correction or adjust time of correction for flickering loads.Size: 2 bytes
Default: 255
Minimum: 0
Maximum: 255
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 255 | Brightness level correction for flickering loads |
35 - Power limit - OVERLOAD
Reaching the defined value will result in turning off the load. Additional apparent power limit of 350VA is active by default. Parameter 39 is relevant only when parameter 58 is set to 0.Size: 2 bytes
Default: 250
Minimum: 0
Maximum: 350
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 350 | Power limit - OVERLOAD |
36 - Response to General Purpose Alarm
0 - No reaction 1 - Turn on the load 2 - Turn off the load 3 - Load blinkingSize: 1 byte
Default: 3
Minimum: 0
Maximum: 3
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 3 | Response to General Purpose Alarm |
37 - Response to Water Flooding Alarm
0 - No reaction 1 - Turn on the load 2 - Turn off the load 3 - Load blinkingSize: 1 byte
Default: 2
Minimum: 0
Maximum: 3
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 3 | Response to Water Flooding Alarm |
38 - Response to Smoke, CO or CO2 Alarm
0 - No reaction 1 - Turn on the load 2 - Turn off the load 3 - Load blinkingSize: 1 byte
Default: 3
Minimum: 0
Maximum: 3
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 3 | Response to Smoke, CO or CO2 Alarm |
39 - Response to Temperature Alarm
0 - No reaction 1 - Turn on the load 2 - Turn off the load 3 - Load blinkingSize: 1 byte
Default: 1
Minimum: 0
Maximum: 3
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 3 | Response to Temperature Alarm |
40 - Time of alarm state
Time of alarm stateSize: 2 bytes
Default: 600
Minimum: 1
Maximum: 32767
Possible values
| From | To | Desription |
|---|---|---|
| 1 | 32767 | Time of alarm state |
41 - OVERLOAD alarm report (load power consumption too high)
0 - No reaction 1 - Send an alarm frameSize: 1 byte
Default: 1
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | OVERLOAD alarm report |
42 - LOAD ERROR alarm report (no load, load failure, burnt out bulb)
0 - No reaction 1 - Send an alarm frameSize: 1 byte
Default: 1
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | LOAD ERROR alarm report |
43 - OVERCURRENT alarm report (short circuit, burnt out bulb causing overcurrent)
0 - No reaction 1 - Send an alarm frameSize: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | OVERCURRENT alarm report |
44 - SURGE alarm report (Dimmer-Control output overvoltage)
0 - No reaction 1 - Send an alarm frameSize: 1 byte
Default: 1
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | SURGE alarm report |
45 - OVERHEAT (critical temperature) and VOLTAGE DROP (low voltage) alarm report
0 - No reaction 1 - Send an alarm frameSize: 1 byte
Default: 1
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | OVERHEAT (critical temperature) and VOLTAGE DROP |
46 - Active power reports
The parameter defines the power level change that will result in a new power report being sent. The value is a percentage of the previous report.Size: 1 byte
Default: 10
Minimum: 0
Maximum: 100
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 100 | Active power reports |
47 - Periodic active power and energy reports
Parameter 52 defines a time period between consecutive reports. Timer is reset and counted from zero after each reportSize: 2 bytes
Default: 3600
Minimum: 0
Maximum: 32767
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 32767 | Periodic active power and energy reports |
48 - Energy reports
Energy level change which will result in sending a new energy report.Size: 2 bytes
Default: 10
Minimum: 0
Maximum: 255
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 255 | Energy reports |
49 - Self-measurement
The Dimmer-Control may include active power and energy consumed by itself in reports sent to the main controller.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 1
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 1 | Self-measurement |
50 - Method of calculating the active power
This parameter defines how to calculate active power. It is useful in a case of 2-wire connection with light sources other than resistive. Parameter 58 is set to 0 after forced auto-calibration.Size: 1 byte
Default: 0
Minimum: 0
Maximum: 2
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 2 | Method of calculating the active power |
51 - Approximated power at the maximum brightness level
This parameter determines the approximate value of the power that will be reported by the device at its maximum brightness level. Parameter 59 works only when parameter 58 has a value other than 0.Size: 2 bytes
Default: 0
Minimum: 0
Maximum: 500
Possible values
| From | To | Desription |
|---|---|---|
| 0 | 500 | Approximated power at the maximum brightness level |
Operating instructions (3)
To add the device to the Z-Wave network manually: 1. Place Dimmer-Control within the direct range of your Z-Wave controller. 2. Identify switch no. 1 (turns the light on) or the B-button (located on the device’s housing). 3. Set the main controller in (security/non-security) add mode (see the controller’s manual). 4. Quickly, three times press switch no. 1 or the B-button. 5. Wait for the adding process to end. 6. Successful adding will be confirmed by the Z-Wave controller’s message.
1. Place Dimmer-Control within the direct range of your Z-Wave controller. 2. Identify switch no. 1 (turns the light on) or the B-button (located on the device’s housing). 3. Set the main controller in remove mode (see the controller’s manual). 4. Quickly, three times press switch no. 1 or the B-button. 5. Wait for the removing process to end. 6. Successful removing will be confirmed by the Z-Wave controller’s message. 7. Dimmer-Control will start the calibration process.
1. Disconnect the power supply. 2. Remove Dimmer-Control from the wall switch box. 3. Connect the power supply. 4. Locate the B-button on the housing. 5. Press and hold the B-button to enter the menu mode. 6. Wait for the visual LED indicator to turn yellow. 7. Quickly release and click the B-button again. 8. After few seconds the device will be restarted, which is signalled with the red LED indicator colour. 9. The device enters the calibration mode.
Document (1)
| Type | Name | |
|---|---|---|
| Product Manual | Dimmer-Control-User Manual.pdf |
Supported notifications (7)
| Group | Type |
|---|---|
| Heat Alarm | Heat sensor status: Overheat detected |
| Power Management |
|
| System | HW status: System hardware failure |
Supported sensor (1)
| Sensor type |
|---|
| Power |
Supported meter (1)
| Meter type |
|---|
| Electric Meter Consumption |